Xem mẫu
- TrueNet Installation Guidelines
C5eT & C6T
Parameter Current Standards TrueNet Recommendation
Horizontal Run Distance 90 Metres No Change
Patch Cable Lengths Total of all patch cables less Total of all patch cables less than
than 10 Metres 10 Metres, but only patch cables
of approved lengths will be
allowed.
Patch Cable Source Unspecified, but do not allow Must be from an approved
specific components source. NO third party patch
cable assembly permitted under
any circumstances
Twists
- Parameter Current Standards TrueNet Recommendation
Block to Block Cross-Connects Specified cable Special designed jacketed cross-
connect cable required (part
number TBD)
Service Loops 3 metres at closet, 1 metre at The cable shall not have more
station than 4 wraps/360 degree loops
Pair Re-twist Not Specified If too much untwist is taken out
during the termination process,
re-twisting is allowed providing
the twist is put pack into the pair
at a rate of one twist per quarter
inch.
Water Migration Not Specified No liquid may penetrate the
cable at connection points or
cable breaks, or the node must
be replaced.
Environment Specified Cables rated for indoor use must
not be stored in an outdoor
environment. Enclosed
temporary facilities are accepted
provided temperature and
humidity considerations are met.
Multiple Cable Pulling Specified The practice of using one cable
to pull multiple cables is not
allowed unless tensioning
devices are employed to
distribute pulling on the group of
cables being installed
nguon tai.lieu . vn