Xem mẫu

  1. Simpo PDF Merge and Split Unregistered Version - http://www.simpopdf.com It is possible to charge refrigerant from an open drum a (8) When the drum is empty, close the valve on the 60° temperatures, although it is recommended that cooler and disconnect the drum. Remove the valve for use with the next drum. Complete charging of the leaktight connections be made to the charging valve. The machine requires 1200 pounds of refrigerant. charging valve is located on the side of the cooler. To 5. Adding refrigerant to bring refrigerant to standard help in the charging procedure, each refrigerant drum has level. When adding refrigerant, use the same procedures a special type plug installed on the side of the drum. that we have just discussed. Another method that can be This plug is specially engineered for charging purposes. used to add refrigerant is simply to allow the refrigerant The charging connection on the drum consists of a 2- to be drawn in as a gas. Let the drum rest on the floor inch plug in which is inserted a smaller 3/4-inch plug. and let the gas escape into the cooler while the machine The 3/4-inch opening inside the drum is covered with a is in operation or idle. friction cap. The cap prevents leakage into or out of the 6. Removing refrigerant. In removing refrigerant drum when the 3/4-inch plug is unscrewed. from the cooler, the following procedure is 4. Refrigerant charging. To charge the machine recommended: with refrigerant, proceed as follows: (1) By use of the purge recovery unit, inject air into (1) The machine must be under a vacuum. the machine until the pressure is 5 pounds gauge. (2) Fit a 3/4-inch nipple into the standard globe (2) Connect tubing to the charging valve on the valve and close the valve. cooler and allow the refrigerant to discharge into the (3) Remove the 3/4-inch plug inserted in the 2-inch refrigerant drum. plug from the drum. (3) Less loss of refrigerant will take place if the (4) Place the valve with the nipple into the opening, refrigerant is cold. Always allow space in the drum for making sure that it is far enough in to push off the cap refrigerant expansion. inside the drum. 7. Troubleshooting. The steps to be taken in (5) Place the drum in a horizontal position near the detecting and correcting improper operation of the cooler charging valve with the use of a hoist. The drum centrifugal machine are outlined in table 19. Use the should be high enough to allow the refrigerant to flow as proper methods for making these service adjustments, a liquid, by gravity, from the drum into the charging line. repairs, and corrections as outlined in this chapter. All Rotate the drum so that the valve is at the bottom. settings, clearances, and adjustments must be made to (6) Connect the two valves (drum and cooler) with manufacture’s specifications. The manufacturer’s a copper tube and fittings, making sure all the joints are maintenance catalog gives definite clearances, leakproof. temperatures, pressure, and positions for adjustment of (7) Open both valves and allow the refrigerant to component parts. These tolerances must be set as flow into the cooler. Operate the machine to maintain a recommended for efficient operation; carelessness in vacuum after the initial reduction to zero. these settings can cause extensive damage to the machine. TABLE 19 70
  2. Simpo PDF Merge and Split Unregistered Version - http://www.simpopdf.com
  3. Simpo PDF Merge and Split Unregistered Version - http://www.simpopdf.com TABLE 19-continued 71
  4. Simpo PDF Merge and Split Unregistered Version - http://www.simpopdf.com TABLE 19-Continued 1. The refrigerant charge is approximately Review Exercises ___________ pounds. (Sec. 9, Par. 1) The following exercises are study aids. Write your answer in pencil in the space provided after each exercise. Use the blank pages to record other notes on the chapter content. Immediately check your answers with the key at the end of the text. 72
  5. Simpo PDF Merge and Split Unregistered Version - http://www.simpopdf.com 2. Which component reduces the horsepower 11. The oil pump is driven from the requirement per ton of refrigeration? (Sec. 9, _____________________. (Sec. 10, Par. 7) Par. 2) 12. Which component does the pump lubricate first? 3. (Agree)(Disagree) The refrigerant flows through (Sec. 10, Par. 8) the tubes in the cooler. (Sec. 9, Par. 3) 13. How is oil returned from the oil pump drive 4. The liquid refrigerant, from the condenser, gear? (Sec. 10, Par. 9) enters the _______________. (Sec. 9, Par. 5) 14. How is the shaft seal actuated? (Sec. 1, Par. 10) 5. How much pressure is there within the economizer chamber? (Sec. 9, Par. 5) 15. What purpose do the two holes in the inner floating seal ring serve? (Sec. 10, Par. 11) 6. The suction gas is taken in by the compressor in _____________ the shaft. (Sec. 10, Par. 1) 16. The automatic stop valve is set to open at approximately ________________ pounds. (Sec. 10, Par. 12) 7. How are the wheels (impellers) protected from corrosion? (Sec. 1, Par. 2) 17. Which oil pressure gauges are mounted on the control panel? (Sec. 10, Par. 13) 8. Each bearing has ______________ large oil rings. (Sec. 10, Par. 3) 18. How is the oil heater energized during shutdown? (Sec. 10; Par. 14) 9. What prevents interstage leakage of gas? (Sec. 10, Par. 4) 19. (Agree)(Disagree) During operation the two polished surfaces of the shaft seal are held together with a spring. (Sec. 10, Par. 16) 10. Which end of the compressor will axial thrust affect? (Sec. 10, Par. 5) 20. What type oil is used in centrifugal compressors? (Sec. 10, Par. 17) 73
  6. Simpo PDF Merge and Split Unregistered Version - http://www.simpopdf.com 21. The compressor gear drive (increases, decreases) 30. The motor furnished with the centrifugal the motor to compressor speed. (Sec. 11, Par. 1) machine is __________ phase, _________________ cycle, and has an ________________ rotor. (Sec. 13, Par. 1) 22. The grade of oil to use on a gear depends on __________, ___________, and ______________.(Sec. 11, Par. 3) 31. The secondary drum control is used to adjust the amount of resistance in the ___________________ of the motor which regulates motor ____________________ 23. When would you turn on the gear drive cooling (Sec. 13, Par. 3) water? (Sec. 11, Par. 5) 32. Which switch is bypassed when the start button 24. Worn bearings in the gear drive will cause is held closed? (Sec. 13, Par. 4) ___________________. (Sec. 11, Par. 9) 33. What is the secondary function of the 25. Which coupling uses a spool piece? (Sec. 12, condenser? (Sec. 14, Par. 1) Par. 1) 34. What prevents the discharge gas from directly 26. How is the hub expanded when it is to be hitting the condenser tubes? (Sec. 14, Par. 2) installed on the shaft? (Sec. 12, Par. 2) 35. What precaution would you observe while 27. The angular alignment of a coupling is checked removing the water box cover? (Sec. 14, Par. 3) with a _________________. (Sec. 12, Par. 3) 36. A burst rupture disc is caused by 28. Which instrument is used to check the offset __________________ (Sec. 14, Par. 6) alignment of a coupling? (Sec. 12, Par. 4) 37. How can you determine the refrigerant charge 29. Which type of coupling can be lubricated while of the system? (Sec. 14, Par. 11) the compressor is running? (Sec. 12, Par. 8) 38. What is indicated when the temperature differential of the refrigerant and chilled water increases? (Sec. 14, Par. 13) 74
  7. Simpo PDF Merge and Split Unregistered Version - http://www.simpopdf.com 39. ________________ is prevented by the hot 48. When are large quantities of air normally purged gas bypass. (Sec. 15, Par. 1) from the centrifugal refrigeration system? (Sec. 16, Par. 10) 40. Why is the liquid injector used in the hot gas bypass? (Sec. 15, Par. 2) 49. When is water drained from the separator unit? (Sec. 16, Par. 12) 41. What controls the amount of liquid refrigerant flowing to the hot gas bypass? (Sec. 15, Par. 3) 50. The four safety controls that will stop the centrifugal are _______________, ________, ___________, and _______________. (Sec. 17, Par. 1) 42. (Agree) (Disagree) The high-pressure control on the purge unit must be reset manually. (Sec. 16, Par. 3) 51. Which safety control does not require manual resetting? (Sec. 17, Par. 2) 43. Where is the weir and trap located on the purge unit? (Sec. 16, Par. 3) 52. What is the differential for the high condenser pressure control? (Sec. 17, Par. 3) 44. High head pressure indicates that ___________________. (Sec. 16, Par. 5) 53. How can you change (switch over) controllers? (Sec. 17, Par. 6) 45. How is the air pressure in the condenser released to the atmosphere? (Sec. 16, Par. 6) 54. The most efficient method of controlling the capacity of the centrifugal is to ____________________. (Sec. 18, Pars. 1 46. What amount of water collected by the purge and 2) unit is an indication of leaky tubes? (Sec. 16, Par. 8) 55. What will occur if you add more resistance to the rotor circuit of the drive motor? (Sec. 18, 47. When will a pressure drop exist across the Par. 3) pressure-regulating valve? (Sec. 16, Par. 9) 56. When is suction damper control more effective than speed control? (Sec. 18, Par. 4) 75
  8. Simpo PDF Merge and Split Unregistered Version - http://www.simpopdf.com 57. What is the position of the drum controller lever 63. What is one of the most probable causes of high during startup? (Sec. 19, Par. 2) condenser pressure? (Sec. 20, table 19) 58. What will cause the oil level to rise in the pump 64. Surging is caused by _________________, chamber during an extended shutdown? (Sec. ________________, or 19, Par. 6) ________________. (Sec. 20, table 19) 59. The pressure within the machine during an oil 65. What would occur if the economizer float valve replacement operation should be approximately stuck? (Sec. 20, table 19) _______________ p.s.i.g. (Sec. 20, Par. 2) 66. What will cause a low "back of seal" oil pressure 60. (Agree)(Disagree) The 2-inch plug in the and a high seal oil pressure? (Sec. 20, table 19) refrigerant drum prevents leakage when the 3/4- inch plug is removed. (Sec. 20, Par. 3) 67. Noisy couplings are caused by ___________________, 61. How is refrigerant charged into the system as a ________________, or gas? (Sec. 20, Par. 5) _________________. (Sec. 20, table 19) 62. How do you pressurize the system to remove 68. (Agree)(Disagree) A high oil level in the speed refrigerant? (Sec. 20, Par. 6) gear will cause the gear to overheat. (Sec. 20, table 19) 76
  9. Simpo PDF Merge and Split Unregistered Version - http://www.simpopdf.com CHAPTER 4 Water Treatment WATER USED IN air-conditioning systems may create you will saturate the water and no amount of stirring problems with equipment, such as scale, corrosion, and would cause any more salt to go into solution. But if you organic growths. Scale formation is one of the greatest heat the water to 100° F., more salt can be dissolved into problems in air-conditioning systems that have water- the solution. This dissolving action is known as direct cooled condensers and cooling towers. Corrosion is solubility. But if you reaccomplish these steps using always a problem in an open water recirculating system in calcium saturates instead of table salt, you would see which water sprays come in contact with air. The more solids precipitate out of the solution as the heat is organic growth we are greatly concerned with is algae or increased. This action is suitably called reverse solubility slime. Since algae thrive on heat and sunlight they will and occurs in a water-cooled condenser cooling tower. be a problem in cooling towers. As a refrigeration specialist or technician you will save the military great 3. You will find that scale will form on heat sums of money if you test and treat your equipment transfer surfaces when you use water containing even a water. For example, if you allowed scale to reach the small amount of hardness. The pH value of the water thickness of a dime in a water-cooled condenser, it would determines if the hard water will cause scale or corrosion. cut the efficiency of the machine more than 50 percent. The pH scale is from 0 to 14. Neutral water has a pH value of 7.0. Any reading under 7.0 is acid, while a reading above 7.0 is base or alkaline. 21. Scale 4. Let us compare pH to temperature. A 1. When water is heated or evaporated, insolubles thermometer measures the temperature of a solution, are deposited on metal surfaces. These deposits usually while pH measures the intensity of acid or base in a occur on the metal in the cooling towers, evaporative solution. As you know, pH means potential hydrogen. condensers, or inside the pipes and tubes of the When a hydrogen atom has lost its electron (H+ ), it condenser water system which have a recirculating water becomes a positive hydrogen ion. When a great many of system. What causes scale? We can explain it in a these hydrogen atoms make this change, the solution will simple formula: become highly acid and attack metals. When the hydrogen atom gains electrons, the solution will be base Ca (HCO3) + heat = CaCO3, + CO2 + H2O and have a pH value from 7.1 to 14. A base solution Calcium calcium carbon contains more hydroxyl ions (OH-). Scale will form bicarbonate + heat = carbonate + dioxide + water when a base solution is exposed to a temperature rise, providing the hardness is 200 parts per million or higher. In this formula the calcium carbonate is the villain. Notice the recommended pH for cooling towers in figure Calcium carbonate is the chief scale-forming deposit found 69. in air-conditioning systems, but magnesium carbonate and calcium sulfate can also cause some degree of scaling. 5. You will find that it is very important to test for solids in the water because solid content (hardness) 2. Causes of Scale . A rising temperature determines the amount of scale formation. Hardness is decreases the solubility of calcium carbonate and calcium the amount of calcium and magnesium compounds in sulfate. This is known as reverse solubility. Sodium solution in the water. Water containing 200 p.p.m. compounds such as table salt (sodium chloride), on the hardness and a pH indication of 9 or above will enhance other hand, have a direct solubility. Suppose you take a the formation of scale. To avoid scale in cooling towers, glass of water 80° F. and dissolve table salt into the you must control hardness. The maximum p.p.m. water. Soon standards for cooling towers are 77
  10. Simpo PDF Merge and Split Unregistered Version - http://www.simpopdf.com titration directly measures the soap-consuming capacity of a water. You will study this test in the following paragraphs. 9. To begin the soap hardness test, measure 50 milliliters of the sample water into the hardness testing bottle. Add the standard soap solution to the water, 0.5 ml. at a time, from the soap burette, shown in figure 70. Shake bottle vigorously after each application and place it on its side. If no lather forms, continue adding 0.5-ml. portions of soap solution to a maximum of 6 ml and place the bottle on its side. Now you must use the formula below if you have a permanent lather to Figure 69. pH scale. complete the test. If a permanent lather does not appear, see para 10. Hardness (p.p.m.) 100 p.p.m. for makeup water and 200 p.p.m. for bleedoff (total number or ml. of standard water. = 20 X soap solution required for permanent lather) 6. In cooling towers and evaporative condensers 10. If a permanent lather does not appear after the water becomes harder due to evaporation. The term adding 6 ml. of the standard soap solution, used to compare hardness to the circulating water to the makeup water is cycles of concentration. For example, 2 cycles of concentration indicate that the circulating water is twice as hard as the makeup water. If the makeup water contained 100 p.p.m., the circulating water would contain 200 p.p.m. To avoid this damaging concentration, you will find it is necessary to limit the cycles of concentration. Bleedoff is an effective method used for this purpose. The amount of bleedoff can be calculated by using the following formula: Cycles of concentration = bleedoff hardness (circulating water) makeup hardness For example: if the bleedoff (circulating water) is 150 p.p.m. and the makeup is 50 p.p.m., the cycles of concentration are 3. 7. There are many methods of treating water to prevent scale. A few of these are: • Bleedoff-regulate the amount of bleedoff water to keep the cycles of concentration within tolerance. • pH adjustment-maintain the pH of the water between 7 and 9, as near 8 as possible. • Add polyphosphates-keeps scale forming compounds in solution. • Zeolite water softening-exchanges a nonscale forming element for calcium and magnesium compounds. Before we discuss water softening, we will introduce the soap hardness test. 8. Soap Hardness Test. The soap hardness test is used to measure total hardness. The presence of calcium and magnesium salts, and to a lesser degree other dissolved minerals, constitutes hardness in water. Hardness can be best determined by soap titration. Soap Figure 70. Soap hardness test equipment. 78
  11. Simpo PDF Merge and Split Unregistered Version - http://www.simpopdf.com Figure 71. Accelator. repeat the test with a new water sample. This time dilute 25 ml. of the sample water with an equal quantity of 13. Zeolite process. The zeolite process is usually zero-hardness water (distilled water). Conduct the test as used for water which has low turbidity and does not you studied previously. When a permanent lather has require filtration. Treatment may be given to the entire been obtained, calculate the hardness as follows: supply at one point. This system is commonly used to soften water for special uses, such as for the control of (total number of ml. of standard scale. In such cases, the treatment units are located at = 40 X soap solution required for points near the equipment requiring treated water. permanent lather) 14. Turbidity is a muddy or unclear condition of 11. Water Softening. Hard waters are potable but water which is caused by suspended silt, clay, sand, or are objectionable because they form scale inside of organic materials such a decaying vegetation or animal plumbing and on metal system components. A waste. Turbidity can be corrected by sedimentation, temporary hardness can be caused by magnesium filtration, or traps. In most cases the water supply and bicarbonate. Hard water can be softened by two sanitation personnel will supply you with usable, potable different methods. The first is the lime-soda process water. which changes calcium and magnesium compounds from soluble to insoluble forms and then removes these 15. Softening devices. Softening devices include insolubles by sedimentation and filtration. The second patented equipment such as the Accelator and Spiractor. and most common is zeolite or base-exchange process. The Accelator is also used as a combined flocculation and This process replaces soluble calcium and magnesium sedimentation unit without softening. When this unit is compounds with soluble sodium compounds. operated before filtration to treat water with low 12. Lime-soda process. Lime-soda process plants are suspended solids and low alkalinity, it may be necessary essentially the same as water filtration plants. Lime and to add lime or clay to add weight and prevent rising floc. soda ash are added to raw water; the softening reaction occurs during mixing and flocculation. The precipitated 16. The Accelator, shown in figure 71, is a calcium and magnesium a removed by sedimentation and suspended solid clarifier. Precipitates which are formed filtration. An additional process, called recarbonation, are kept in motion by a combination of mechanical which is the introduction of carbon dioxide gas, is agitation and hydraulic flow. Velocity of waterflow frequently applied immediately prior to filtration. If the through the system is controlled to keep precipitates in raw water has high turbidity, the turbidity suspension at a level where water passes through them. is partial removed by sedimentation prior to the adding of The accumulated the lime and soda. 79
  12. Simpo PDF Merge and Split Unregistered Version - http://www.simpopdf.com with a swirling motion. The upward velocity keeps the granular material in suspension. As the water rises, velocity decreases to a point where material is no longer in suspension. The contact time, 8 to 10 minutes, is enough to complete softening actions. Softened water is drawn off from the top of the cone. The size of calcium carbonate granules increases during the process, increasing the bulk of granules in the unit. The water level of the cone is kept down to the desired point by withdrawing the largest particles from the bottom. New material must be added, which can be produced by regrinding and screening the discharged material. Softened water is usually filtered through a sand filter to move turbidity. Advantages of the equipment are its small size, low installation cost, rapid treatment lack of moving parts and pumping equipment, and elimination of sludge disposal problems. The unit is most effective when hardness is predominantly calcium, there is less than 17 p.p.m. magnesium hardness (expressed as calcium carbonate), water temperature is about 50° F., and turbidity is less than 5 p.p.m. 18. Zeolite (ion exchange). Ion exchange is a chemical operation by which certain minerals that are ionized or dissociated in solution are exchanged (and thus removed) for other ions that are contained in a solid exchange medium, such as a zeolite sandbed. An example is the exchange of calcium and magnesium, in solution as hardness in water, for sodium contained in a sodium zeolite bed. The zeolites used in the process of ion exchange are insoluble, granular materials. A zeolite may be classified as follows: glauconite (or green sand), precipitated synthetic, organic (carbonaceus), synthetic Figure 72. Spiractor resin, and clay. Various zeolites are used, depending on the type of water treatment required. Most zeolites precipitate is called the sludge blanket. When the possess the property cation, or base exchange, but anion Accelator is operating properly, the water above the exchangers are also available and may be used when sludge blanket and flowing over the weirs is clear. demineralization of water is required. In the course of Operation depends on balancing the lift of particles by treating water, the capacity of the zeolite bed to exchange the velocity of upward flowing water against the pull of ions is depleted. This depletion requires the bed to be gravity. When the velocity of the water is gradually regenerated by the use of some chemical that contains decreased, a point is reached at which the particles are the specific ion needed for the exchange. For instance, too heavy to be supported by the velocity of the water. when a sodium zeolite is used to soften water by Continuous treatment builds up the sludge blanket which exchanging the sodium ion for the calcium and is drawn off as required. Operation of the equipment is magnesium ions of hard water, the zeolite gradually covered in detail in the manufacturer’s instruction becomes depleted of the sodium ion. Thus, it will not manuals. take up the calcium and magnesium ions from the water 17. The Spiractor, shown in figure 72, consists of an passing through the bed. The sodium ion is restored to inverted conical tank in which the lime-soda softening the zeolite by uniformly distributing a salt or brine reactions take place in the presence of a suspended bed solution on top of the bed and permitting it to pass of granular calcium carbonate. In operation, the tank is evenly down through the bed. The salt removes the slightly more than half filled with 0.1 to 0.2 millimeter calcium and magnesium taken up by the bed as soluble granules. Hardwater and chemicals enter the bottom of chlorides and restores the zeolite to its original condition. the unit close to each other. They mix immediately as Beds may also be regenerated with acid, sodium the treated stream of water rises through the granular bed carbonate, 80
  13. Simpo PDF Merge and Split Unregistered Version - http://www.simpopdf.com sodium hydroxide, or potassium permanganate, depending 7. Erosion-corrosion. Erosion-corrosion is caused by on the type of zeolite being used. suspended matter or air bubbles in a rapidly moving 19. In addition to the problem of scale, the water. The matter can be fine to coarse sand, depending refrigeration man knows that corrosion is a constant on the velocity of the water. Usually the greatest amount problem. Let us now study corrosion, its causes, its of erosion-corrosion will take place at elbows and U- effects, and its control. bends. Another place where erosion-corrosion takes place is on the impellers of centrifugal pumps. 22. Corrosion 8. Good filtration installations will remove grains 1. In the refrigeration/air-conditioning field, of sand and other matter that are large enough to cause corrosion has long been a problem. Even in the modern erosion-corrosion. To get rid of air tapped in a system, it missile complexes, corrosion is prevalent. Corrosion is is recommended that hand- or spring-operated bleed very difficult to prevent, but it can be controlled. Before valves be installed in the highest point of the water we can control corrosion, we first must understand what system. Purging the water system gets rid of the air causes it. bubbles that enter the system in the makeup water. 2. The effects of corrosion differ as to the type of corrosion, such as uniform, pitting, galvanic, erosion- 9. Electrochemical corrosion. Electrochemical corrosion, and electrochemical. We must understand corrosion occurs when a difference in electrical potential various ways of treating the system to control these types exists between two parts of a metal in contact with an of corrosion. Corrosion is generally more rapid in liquids electrolyte (water). The difference in potential will cause with a low pH factor than in alkaline solutions. electric current to flow. The difference in potential may 3. Types of Corrosion. An air-conditioning system be set up by two dissimilar metals, by a difference in may have several types of corrosion in the water system. temperature or amount of oxygen, or by the Many of these types are undoubtedly familiar to you. concentration of the electrolyte at the two points of 4. Uniform corrosion. One of the most common contact with the metal. The anode is the point at which types of corrosion encountered in acid environments is the current flow is from the metal to the electrolyte; it is known as uniform corrosion. This is caused by acids, here that corrosion occurs. The cathode, which is usually such as carbonic, which cause a uniform loss of metal not attached, is the point of current flow from the throughout the condensating water system. electrolyte to the metal. This action is shown in figure 5. Pitting corrosion. Pitting corrosion is a 73. nonuniform type, the result of a local cell action produced when a particle, flake, or bubble of gas 10. Corrosion Inhibitor. The most common deposited on a metal surface. The pitting is a local chemicals used as inhibitors are chromates and accelerated attack, which causes a cavity in the metal but polyphosphates. These inhibitors alone serve only to does not affect the surrounding metal. Oxygen decease the rate of corrosion, but if other water deficiency under such a deposit sets up an anodic action. treatments are used in conjunction with them, corrosion This area keeps producing such action until the may be nearly stopped. penetration finally weakens the structure and it falls, developing a pinhole leak. 11. Chromates. Chromates are seldom present n 6. Galvanic corrosion. When dissimilar metals untreated water; however, they may occur as a result of which are capable of carrying electric current are present industrial waste contamination. The chromates are used in a solution, galvanic corrosion occurs. This action is extensively to inhibit corrosion and are effective in the similar to the electroplating process used in industry to water air-conditioning systems in concentrations of 200- bond or plate dissimilar metals. When two metals similar 500 p.p.m. at a pH of 7.0 to 8.5. Chromates are the to each other are joined together, there is little reaction. most commonly used corrosion inhibitors in chilled water But the coupling of two metals from different groups systems. For corrosion prevention the most favorable causes accelerated corrosion in one of the two metals. range is with the pH from 7.5 to 9.5, but scaling becomes When using large amounts of copper in a system and a a problem at the higher pH range. Consequently, the pH few unions of steel, the steel will corrode at a rapid rate. should be held near the lower range where corrosion In such cases you should install nonferrous metal instead protection is excellent. Because it is more economical, of steel. Corrosion inhibitors reduce the corrosion rate sodium bichromate (Na2Cr2O72H2O) is the most but will not eliminate galvanic corrosion. commonly used chromate compound. Sodium chromate (Na2CrO4) is also used widely. 12. Chromate concentration is stated in p.p.m. 81
nguon tai.lieu . vn